insulation oil purification machine, cable oil purifier, used transformer oil regeneration and recondition system, dielectric oil reclamation
$1/set
Application:
ZYD-I double stage vacuum transformer oil regeneration equipment is specially designed for on site use to completely purify and regenerate insulating oils in energized or de-energized transformers. It can regenerate and recycle the old aging transformer oil to approximate new oil. Provide regular oil purification including degassing, drying and particulate removal but also remove acidity, sludge, other soluble oil decay products, and improve color. For special application, the system also can be mounted on a leak proof base or be installed and operated on a trailer.
Features:
1. For special application, the operation can be controlled by P.L.C (Programmable Logic Controller).
2. Unique vacuum dehydration, degassification and regeneration system, adopt stereo-evaporation technology. Duplex 3D stereo-evaporation, eliminating the liquid water quickly.
3. UK g technology by which the trace water that is show chain, such as dissolved water, can be removed effectively.
4. Advanced infrared liquid-level automatic control system to accomplish fully automatic control.
5. Can be applied for vacuum oiling and drying power transmission equipment.
6. Special additives for depolarization can recover oil color of aged transformer oil to new.
Technical Parameters
Parameter | Unit | ZYD-I-30 | ZYD-I-50 | ZYD-I-100 | ZYD-I-150 | ZYD-I-200 | ZYD-I-250 | ZYD-I-300 |
Flow rate | L/h | 1800 | 3000 | 6000 | 9000 | 12000 | 15000 | 18000 |
Working vacuum | MPa | -0.08~-0.099 | ||||||
Working pressure | MPa | ≤0.3 | ||||||
Temperature | ℃ | 20 ~ 80 | ||||||
Power | 3 ph 380V 60Hz (Or as needed) please contact HOPU salesman | |||||||
Working noise | dB(A) | 75 | 75 | 75 | 75 | 80 | 80 | 80 |
Heating power | kW | 30 | 30 | 45 | 60 | 75 | 90 | 120 |
Total power | kW | 35.5 | 37.5 | 52.5 | 71.4 | 86.5 | 102.5 | 135 |
Oil Inlet/Outlet | mm | φ25 | φ32 | φ42 | φ50 | φ50 | φ60 | φ60 |
Weight | Kg | 600 | 800 | 1050 | 1400 | 1800 | 2000 | 2200 |
Size | L,mm | 1050 | 1100 | 1200 | 1450 | 1600 | 1800 | 1900 |
W,mm | 750 | 800 | 950 | 950 | 1100 | 1200 | 1200 | |
H,mm | 1350 | 1400 | 1500 | 1650 | 1800 | 1900 | 1900 |
Oil Index After Treated by ZYD-I Machine
Item | Unit | After treatment |
Breakdown Voltage | kV | ≥75 |
Moisture content | PPM | ≤3 |
Gas content | % | ≤0.1 |
Impurity size | micron | ≤0.5 (no free carbon) |
IFT | dynes/cm | ≥40 |
Acid value | mg KOH/g | ≤ 0.03 |
Dielectric loss factors | tgδ(90°C) | ≤0.001 |
Colour | L | ≤0.5 |
Please contact for more technical details and latest price:
Michael Hua is at your service
Email 1: mh@hopufiltration.com
Email 2: oilfilter@aliyun.com
QQ:330713880
Mob: 0086 13896055638 (what's App for online inquiry)
Tel: +86 23 62538144
Fax:+ 86 23 62538144-3
Website: www.hopufiltration.com
Branch 1: www.oilpurifiertech.com
Branch 2: www.oilfiltration123.com
Industry Category | General-Industrial-Equipment/Filter-Supplies/Other-Filter-Supplies |
---|---|
Product Category | ZYD-I Transformer Oil Regeneration Plant |
Brand: | HOPU |
Spec: | Flow Capacity: 1800 To 18000 Liters Per Hour; Power Supply::380V,3P,50HZ Or As You Require |
Stock: | |
Origin: |