3.1 Key Specifications/Special Features

Ratings

Power supply voltage  
Power consumption 24 VAC/DC: 1.8 VA/1 W max. 
100 to 240 VAC: 2.5 VA max.
Rated insulation 
voltage
600 VAC
Operating value setting 
range (SV)
10% to 100% of maximum setting range 
Operating value 100% operation at set value
Reset value setting range (HYS) 5% to 50% of operating value
Reset method Note:Manual reset: Turn OFF power supply for 
1 s or longer.
Operating time setting 
range (T)
3to8 s
Indicators   Normal : Green light; Overvoltage Undervoltage : Yellow light
Output form    one Normally open and one normally closed
Output relay ratings Rated load 
5 A at 250 VAC (Resistive load) 
5 A at 30 VDC (Resistive load) 
1 A at 250 VAC (Inductive load) 
0.2 A at 48 VDC (Inductive load) 
Minimum load: 5 VDC, 10 mA (reference values) 
Mechanical life: 10 million operations min. 
Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 
operations 
3 A at 250 VAC or 30 VDC: 
100,000 operations
Ambient operating 
temperature
-20 to 60°C (with no condensation or icing)
Storage temperature -25 to 65°C (with no condensation or icing)
Ambient operating 
humidity
25% to 85% RH (with no condensation)
Storage humidity 25% to 85% RH (with no condensation)
Altitude 2,000 m max.
Applicable wires Stranded wires, solid wires, or ferrules
Applicable wire size 0.25 to 1.5 mm2(AWG24 to AWG16)
Wire insertion force 8 N max. for AWG20 wire
Screwdriver insertion force 15 N max.
Wire stripping length 8 mm
Ferrule length 8 mm
Current capacity 10 A (per pole)
Weight Approx. 60 g
Mounting Mounts to DIN Track
Dimensions 30 *60 *76 mm (W*H*D)

Specifications

Conforming 
standards
EN 60947-5-1 
Installation environment (pollution level 2, Overvoltage category III)
Insulation resistance 20 MΩmin. 
Between external terminals and case 
Between power supply terminals and input terminals 
Between power supply terminals and output terminals 
Between input terminals and output terminals
Dielectric strength 2,000 VAC for one minute 
Between external terminals and case 
Between power supply terminals and input terminals 
Between power supply terminals and output terminals 
Between input terminals and output terminals
Impulse withstand 
voltage
6 kV (between live terminals and exposed, non-charged metal parts)
Vibration resistance Frequency: 10 to 55 Hz, 0.35-mm single amplitude 
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20

 